EPA 608 Required Evacuation Levels, Explained
Updated October 26, 2026
Before an appliance is opened for service or disposal, its refrigerant must be recovered down to a required level of vacuum. These levels come up on the Type II and Type III sections of the EPA 608 exam, and they’re easy to mix up. Here’s the table from the regulation (40 CFR 82.156, Table 1), and how to read it.
The table
Levels are in inches of mercury vacuum, except low-pressure appliances, which use millimeters of mercury absolute. The columns depend on when the recovery or recycling equipment was made, not when the appliance was made.
| Appliance type | Recovery equipment made before Nov 15, 1993 | Recovery equipment made on or after Nov 15, 1993 |
|---|---|---|
| Very high-pressure appliance | 0 | 0 |
| High-pressure, full charge under 200 lb | 0 | 0 |
| High-pressure, full charge of 200 lb or more | 4 | 10 |
| Medium-pressure, full charge under 200 lb | 4 | 10 |
| Medium-pressure, full charge of 200 lb or more | 4 | 15 |
| Low-pressure appliance | 25 mm Hg absolute | 25 mm Hg absolute |
How to read it
- Find the pressure class. Most residential and light commercial systems (R-22, R-410A, R-134a) are high-pressure. Centrifugal chillers using R-123 or R-11 are low-pressure.
- Check the full charge. The 200-pound line splits large systems from small ones.
- Check the recovery equipment’s date. Newer equipment must pull a deeper vacuum on the larger systems.
A useful pattern: newer recovery equipment never has a lower requirement than older equipment, and larger charges never have a lower requirement than smaller ones in the same class.
Small appliances are different
Small appliances (factory-sealed with 5 pounds or less, covered by Type I) don’t use Table 1. With recovery equipment made on or after November 15, 1993, you must recover 90% of the refrigerant if the compressor runs or 80% if it doesn’t. Equipment made before that date must recover 80%. Either way, evacuating to 4 inches of mercury vacuum also meets the requirement.
When a system can’t reach the level
If leaks make it impossible to reach the required level, or reaching it would contaminate the refrigerant, the rules allow recovery to stop at the lowest level that can be reached, within limits. Check the current regulation for the details before relying on this.
Test yourself
-
A medium-pressure appliance with a 250-pound charge is being opened. The recovery machine was made in 2018. What is the required evacuation level?Answer: DMedium-pressure with a full charge of 200 pounds or more, using recovery equipment made on or after November 15, 1993, requires 15 inches of mercury vacuum.
-
A high-pressure appliance with a 250-pound charge is being opened using recovery equipment made in 1990. What is the required evacuation level?Answer: BA high-pressure appliance with 200 pounds or more needs 4 inches of mercury vacuum with recovery equipment made before November 15, 1993, or 10 inches with newer equipment.
-
A residential heat pump with 12 pounds of R-410A is being opened using a recovery machine made in 2022. What is the required evacuation level?Answer: AR-410A is a high-pressure refrigerant, and a charge under 200 pounds needs 0 inches of mercury vacuum regardless of the recovery equipment's age.
-
Which appliances must be evacuated to 25 mm Hg absolute?Answer: CLow-pressure appliances, such as centrifugal chillers using R-123, must be evacuated to 25 mm Hg absolute, a deep vacuum, whatever the recovery equipment's age.
Practise more: Type II practice test, Type III practice test and Type I practice test.
Pass the EPA 608 exam on your first try
- All 168 questions across Core, Type I, Type II and Type III
- An explanation for every answer, with the rule or principle behind it
- Unlimited practice exams per section, scored like the real test (18 of 25 to pass)