EPA 608 Universal Practice Test
Updated October 27, 2026
EPA 608 Universal certification means you passed all four sections of the exam: Core, Type I (small appliances), Type II (high-pressure equipment) and Type III (low-pressure equipment). Each section has 25 questions, and on the standard proctored exam you need 18 right (70%) in each one. Universal lets you work on every kind of stationary refrigeration and air-conditioning equipment.
The free questions below mix all four sections, the way a Universal candidate needs to know them.
Free EPA 608 Universal practice questions
-
To earn Universal certification, which sections must you pass?Answer: BUniversal certification requires passing Core plus all three types. Passing Core and one or two types certifies you for those types only.
-
(Core) Which refrigerant has an ozone depletion potential of zero?Answer: CR-134a is an HFC and contains no chlorine, so its ozone depletion potential is zero. R-12 and R-11 are CFCs, and R-22 is an HCFC.
-
(Core) A recovery cylinder should be filled to no more than what share of its capacity by liquid volume?Answer: CFill recovery cylinders to no more than 80% of capacity by liquid volume, leaving room for the liquid to expand as it warms.
-
(Type I) A small appliance is defined as factory-made, charged and hermetically sealed equipment with:Answer: ASmall appliances are manufactured, charged and hermetically sealed in a factory with 5 pounds of refrigerant or less, such as household refrigerators and window air conditioners.
-
(Type I) With recovery equipment made after November 15, 1993, how much refrigerant must be recovered from a small appliance whose compressor does not run?Answer: CWith a non-operating compressor, 80% must be recovered (90% if the compressor runs), or the appliance can be evacuated to 4 inches of mercury vacuum.
-
(Type II) A comfort cooling appliance with 60 pounds of R-22 must have leaks repaired when its annual leak rate exceeds:Answer: AFor appliances with 50 pounds or more of ozone-depleting refrigerant, the leak-rate threshold is 10% for comfort cooling, 20% for commercial refrigeration and 30% for industrial process refrigeration.
-
(Type III) Why is a purge unit needed on a low-pressure chiller?Answer: ALow-pressure chillers run partly in a vacuum, so leaks pull in air and moisture. The purge unit removes these non-condensables.
-
(Type III) A low-pressure appliance must be evacuated to what level before it is opened?Answer: DEPA requires low-pressure appliances to be evacuated to 25 mm Hg absolute, regardless of when the recovery equipment was made.
-
(Core) What does reclaiming refrigerant require that recycling does not?Answer: BReclaimed refrigerant must meet the AHRI 700 purity standard, verified by chemical analysis. Recycling only cleans refrigerant on site, with oil separation and filter-driers.
-
(Core) Why must refrigerant cylinders never be heated with an open flame?Answer: CHeating raises cylinder pressure and can rupture the cylinder, and refrigerant exposed to flame breaks down into toxic products such as phosgene and acids.
-
(Type I) Small appliances using hydrocarbon refrigerants such as R-290 require:Answer: DR-290 (propane) and R-600a (isobutane) are highly flammable (safety group A3). Avoid ignition sources, ventilate and use equipment rated for flammable refrigerants.
-
(Type II) Under EPA's definitions, R-134a appliances are classified as:Answer: A40 CFR 82.152 lists R-134a and R-12 as medium-pressure refrigerants. Medium-pressure appliances are covered by Type II.
-
(Type II) After evacuating a system, which reading shows the system is dry and holds vacuum?Answer: BA micron gauge that reaches a deep vacuum and holds steady, without a rise, shows moisture has been removed and the system doesn't leak. Follow the equipment manufacturer's target level.
-
(Type III) What is usually the first sign of a leak in a low-pressure chiller?Answer: CLow-pressure chillers run partly in a vacuum, so leaks pull air in. The purge unit removes that air, so a rise in purge run time is often the first sign of a leak.
-
(Type III) When a low-pressure chiller in a deep vacuum is charged, why is vapor introduced first?Answer: DLiquid refrigerant entering a system in deep vacuum boils at a very low temperature and can freeze the water in the tubes. Charging vapor first raises the pressure until the saturation temperature is above freezing.